Übersetzen...
0100

CW Limit Stop Input Signal

Omron · SYSMAC CJ Series PLC

Was bedeutet 0100 ?

This fault indicates that the pulse output operation was stopped due to a CW limit signal input. This typically occurs during an origin search function, signifying that the machine has reached its positive travel limit, preventing further movement in the CW direction.

Häufige Ursachen

  • CW limit switch physically activated during an origin search.
  • Miswiring of the CW limit signal input, causing a false trigger.
  • Incorrect 'Limit Input Signal Type' (NC or NO) configured in PLC Setup for the CW limit switch.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Manually move the driven axis in the CCW (counter-clockwise) direction until the CW limit switch is physically disengaged.

  2. 2

    Measure continuity or voltage at the CW limit input terminal to verify signal status (ON/OFF) and expected voltage level (e.g., 24VDC for ON, 0VDC for OFF) based on the configured 'Limit Input Signal Type' in PLC Setup.

  3. 3

    Access the PLC Setup 'I/O Module Tab Page' using CX-Programmer and verify the 'Limit Input Signal Type' parameter is correctly set to 'NC (Normally Closed)' or 'NO (Normally Open)' matching the physical switch.

Alle Codes in diesem Handbuch durchsuchen (20)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes