Ethernet communication fault
Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
Was bedeutet EHR ?
This fault appears when Ethernet communication is interrupted by physical factors, especially when Pr.1431 (Ethernet signal loss detection function selection) is set to a value between '1' and '3'. It signifies a physical layer problem with the Ethernet connection to the inverter.
Häufige Ursachen
- Disconnected or damaged Ethernet cable (RJ45 connector, internal conductors).
- Network switch or router failure preventing data transmission.
- Incorrect IP address, subnet mask, or gateway settings on the inverter (e.g., Pr.1408 to Pr.1413).
- Excessive network traffic (broadcast storms) or collisions causing communication timeouts.
- Physical damage to the inverter's Ethernet port or internal communication module.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the physical Ethernet cable connection at both the inverter and the network switch, ensuring the cable is securely latched.
- 2
Check the link status LEDs on the inverter's Ethernet port and the connected network switch port (should be green/solid).
- 3
Ping the inverter's IP address (set in Pr.1409) from a connected network device to verify basic network connectivity.
- 4
Inspect the Ethernet cable for physical damage (kinks, cuts) and test its continuity using an Ethernet cable tester.
- 5
Review Pr.1431 (Ethernet signal loss detection function selection) and associated timeout parameters to ensure they are appropriate for the network environment.