Übersetzen...
DIP

Duplicate IP address

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

Was bedeutet DIP ?

This warning appears when the inverter detects that its assigned IP address is already in use by another device on the network. This conflict prevents proper network communication and can cause system instability.

Häufige Ursachen

  • Manual assignment of a static IP address to the inverter that is already in use by another device (e.g., PLC, HMI).
  • DHCP server incorrectly assigning the same IP address to multiple devices.
  • Device on the network with a misconfigured IP address (e.g., set to the inverter's IP by mistake).
  • Failure of the inverter or another device to properly release a previous IP address.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the inverter's assigned IP address (Pr.1409) against the network's IP address scheme and other connected devices using a network scanner or 'arp -a' command.

  2. 2

    Temporarily set the inverter's IP address (Pr.1409) to a known unused IP address within the subnet.

  3. 3

    If using DHCP, ensure the DHCP server is configured correctly and check its lease table for duplicate assignments.

  4. 4

    Disconnect suspected duplicate devices one by one from the network to identify the conflicting device.

  5. 5

    Cycle power on the inverter and the suspected conflicting device to force them to re-negotiate or release IP addresses.

Alle Codes in diesem Handbuch durchsuchen (55)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi FR-E800 Variable Frequency Drive