Übersetzen...
E.OHT

Ext TH relay oper

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

Was bedeutet E.OHT ?

The inverter output is shut off because an external thermal relay (for motor overheat protection) or an internally mounted motor thermal relay has activated (contacts open). This protective shutdown prevents motor damage from excessive temperature, and is active when '7' (OH signal) is assigned to Pr.178-Pr.184.

Häufige Ursachen

  • External thermal relay operated.
  • An external overload protection device has tripped.
  • Motor overheating detected by external sensor.
  • Wiring fault to the external thermal relay.
  • External control signal indicating thermal trip.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check for motor overheating; reduce the load and/or operation duty if necessary.

  2. 2

    Verify that the OH signal (value '7') is correctly assigned to one of the input terminal function selection parameters (Pr.178 to Pr.184).

  3. 3

    Reset the inverter after the thermal relay contacts close; the inverter will not restart automatically until reset.

Alle Codes in diesem Handbuch durchsuchen (55)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi FR-E800 Variable Frequency Drive