Übersetzen...
F112
Faulty Loop Status / Mixed Network Modules
Mitsubishi Electric · MELSEC Q-series MELSECNET/H
Was bedeutet F112 ?
The network loop is in a faulty state, indicating a serious communication problem. This can be caused by physical network issues or incompatible network module types being mixed within the same system.
Häufige Ursachen
- Faulty network cables or incorrect cable wirings
- Faulty network hardware
- Electrical noise
- Duplicate station numbers or duplicate control/remote master stations
- Mixing of MESLECNET/H and MELSECNET/10 network modules in the same system
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect network cables for damage, integrity, and correct wiring
- 2
Check for sources of electrical noise impacting communication
- 3
Verify all station numbers are unique
- 4
Confirm control station and remote master station settings are not duplicated
- 5
Ensure that only one type of network module (e.g., MESLECNET/H or MELSECNET/10) is used within the same network, matching the control station type
- 6
Check for faulty network hardware
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Mitsubishi Electric MELSEC Q-series MELSECNET/H