Was bedeutet F107 ?
The network's baton pass mechanism has failed, resulting in a lost baton. This prevents proper communication and data exchange across the network.
Häufige Ursachen
- Faulty network cable
- Uninstalled terminating resistor on the network line
- One or more network stations are not powered on
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect the entire network line for any faulty cables or physical damage
- 2
Verify the correct installation and integrity of all terminating resistors on the network bus
- 3
Confirm that all stations connected to the network are properly powered on
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026