F10F

Number of Send Error Retries Exceeded

Mitsubishi Electric · MELSEC Q-series MELSECNET/H

Was bedeutet F10F ?

The system has attempted to send data multiple times but consistently failed, exceeding the allowed number of retries. This indicates a persistent communication issue on the sending end.

Häufige Ursachen

  • Persistent network communication problems preventing successful data transmission
  • Faulty cables or incorrect wiring
  • Absence of terminating resistors (in bus networks)
  • Duplicate station numbers or duplicate control/master stations
  • Faulty network hardware at the sending station

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect network cables for physical faults or incorrect wiring

  2. 2

    Verify the presence and correct installation of terminating resistors on the bus network

  3. 3

    Check for sources of electrical noise near network cabling

  4. 4

    Verify station numbers and control/remote master station settings for any duplication

  5. 5

    Check for faulty network hardware at the sending station

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026