2440H

Module major error

Mitsubishi Electric · MELSEC iQ-R Series

Was bedeutet 2440H ?

A major error has occurred within a module, regardless of specific "CPU Module Operation Setting at Error Detected" parameters explicitly configured to stop. This error indicates a serious condition that significantly impacts module functionality and system operation. If the "Direct change setting" is enabled, the system might continue operation without stopping, but the error itself will persist.

Häufige Ursachen

  • A major fault condition occurred in a module.
  • A module was physically removed or experienced a failure during operation while "Direct change setting" was enabled.
  • The module's operation setting at error detection might not be explicitly configured to stop for this type of major error.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the "Direct change setting" parameter at [Parameter] -> Module model name -> [CPU Parameter] -> "RAS Setting" -> "Online module change setting".

  2. 2

    Before removing a module, ensure the external power supply input to the module is shut off.

  3. 3

    If the error remains and affects the system with "Direct change setting" enabled, set it to "Disable" and perform an online module change using special relays and special registers.

Alle Codes in diesem Handbuch durchsuchen (9)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026