Module verification error
Mitsubishi Electric · MELSEC iQ-R Series
Was bedeutet 2401H ?
The system detected an issue during module verification. This error indicates a discrepancy or problem during the module's verification process. If the "Direct change setting" is enabled, the system might continue operation without stopping, but the error itself will persist.
Häufige Ursachen
- The "CPU Module Operation Setting at Error Detected Module Verify Error" parameter is set to "Stop".
- A discrepancy occurred during module verification.
- A module was physically removed or experienced a failure during operation while "Direct change setting" was enabled.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the "Direct change setting" parameter at [Parameter] -> Module model name -> [CPU Parameter] -> "RAS Setting" -> "Online module change setting".
- 2
Check the "CPU Module Operation Setting at Error Detected Module Verify Error" setting.
- 3
If the error remains and affects the system with "Direct change setting" enabled, set it to "Disable" and perform an online module change using special relays and special registers.