Übersetzen...
Parameter storage device fault

Parameter Storage Device Fault

Mitsubishi Electric · FR-D700 Inverter

Was bedeutet Parameter storage device fault ?

An abnormality has occurred in the component (control circuit board) where parameters are stored. This suggests a hardware issue with the inverter's non-volatile memory, potentially leading to incorrect operation, loss of critical settings, or failure to save new parameters. Frequent parameter writes for communication purposes can stress this component.

Häufige Ursachen

  • Internal EEPROM (Electrically Erasable Programmable Read-Only Memory) or Flash memory corruption due to power transient.
  • Degradation or failure of the non-volatile memory chip on the inverter's control board.
  • EMI (Electromagnetic Interference) causing data corruption during parameter writes or reads.
  • Manufacturing defect in the memory module or its associated control circuitry.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Document all current parameter settings by manually recording them or using configuration software (e.g., FR-Configurator2).

  2. 2

    Attempt to initialize all parameters to their factory default settings (e.g., Pr. 77 set to 1 or 2, then cycle power).

  3. 3

    Re-enter all necessary parameters from the recorded list after initialization.

  4. 4

    Perform a firmware update for the inverter to potentially overwrite corrupted memory sectors (if applicable).

  5. 5

    If the fault persists, replacement of the inverter's control board is necessary as the memory device is typically integrated.

Alle Codes in diesem Handbuch durchsuchen (78)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi Electric FR-D700 Inverter