Übersetzen...
Analog input fault

Analog Input Fault

Mitsubishi Electric · FR-D700 Inverter

Was bedeutet Analog input fault ?

A voltage (or current) has been input to terminal 4 when the setting in Pr. 267 Terminal 4 input selection and the physical voltage/current input switch on the inverter are mismatched. This incorrect input configuration can lead to erroneous frequency commands, unstable operation, or potentially damage the analog input circuit if not corrected.

Häufige Ursachen

  • Physical switch on the inverter's control board for terminal 4 (voltage/current selection) is set incorrectly.
  • Pr. 267 (Terminal 4 input selection) parameter does not match the desired input signal type (e.g., 0-10V vs. 4-20mA).
  • Incorrect wiring to terminal 4; e.g., current source connected when configured for voltage input or vice-versa.
  • Input signal exceeds the configured range (e.g., >10V when set for 0-10V, or >20mA when set for 4-20mA).
  • Loose connection at terminal 4 or terminal 5 (common) causing an intermittent signal loss or distortion.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Power OFF the inverter, verify the physical voltage/current selection switch for terminal 4 on the control board matches the intended signal type.

  2. 2

    Check Pr. 267 (Terminal 4 input selection) and adjust it to match the physical switch setting and the connected sensor output.

  3. 3

    Measure the input signal voltage (0-10VDC) or current (4-20mA) at terminals 4 and 5 (common) using a multimeter.

  4. 4

    Inspect the wiring to terminals 4 and 5 for proper polarity, secure connections, and absence of shorts.

  5. 5

    Disconnect the external signal source and measure the resistance between terminals 4 and 5 to check for internal input impedance issues (rare).

Alle Codes in diesem Handbuch durchsuchen (78)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Mitsubishi Electric FR-D700 Inverter