E32
Mains Power Phase Reversal / Open Phase Detection
Mitsubishi Electric · FR-D700 Inverter
Was bedeutet E32 ?
The anti-phase device has detected that two phases of the mains power need to be swapped, indicating a phase reversal. Alternatively, the L2 phase of the mains power (primary side of contactor) has been detected as open, leading to unbalanced power.
Häufige Ursachen
- Power supply phase sequence is reversed (e.g., L1-L2-L3 instead of L1-L3-L2).
- One phase of the main AC power supply is missing (open phase).
- Internal power module protection against phase reversal.
- Incorrect wiring at the main power input terminals.
- Power source unstable with fluctuating phase presence.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the phase sequence of the mains power supply using a phase rotation meter. If reversed, correct the L1, L2, L3 phase connections at the outdoor unit.
- 2
Measure the voltage across all phases (L1-L2, L2-L3, L3-L1) at the primary side of the contactor to check for an open L2 phase.
- 3
Inspect the contactor for proper operation, looking for signs of pitting or loose connections at the terminals.