E14
Master/Slave System Control Wiring Error / SW Setting Error
Mitsubishi Electric · FR-D700 Inverter
Was bedeutet E14 ?
This indicates an incorrect setting of DIP switches (SWS) on the indoor unit PCB when configuring a master/slave system. It also points to incorrect control wiring or an open circuit in the control wiring between master and slave units.
Häufige Ursachen
- Incorrect wiring between master and slave units.
- Master/slave configuration switch (e.g., SW4) set incorrectly.
- Communication wiring between master and slave is reversed or incomplete.
- Incorrect SW setting for system operation mode.
- Faulty communication interface on master or slave unit.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the SWS settings on the indoor unit PCB, ensuring they are correct for master/slave configuration.
- 2
Inspect the control wiring between master and slave unit(s) for correct connections.
- 3
Check the continuity of the control wiring between master and slave unit(s) to detect any open circuits.