Motor parameter identification fault
Lenze · i550 Protec Drive
Was bedeutet 65305 ?
An error occurred during the automatic identification process of the connected motor. This indicates a mismatch between the drive's expectation and the motor's actual electrical characteristics or a problem with motor wiring. This could lead to incorrect motor operation or damage.
Häufige Ursachen
- Motor not correctly wired to the drive (U, V, W terminals), or a phase is open-circuited during the identification process.
- Incorrect motor nameplate data (e.g., P300.00-P304.00) entered into the drive's parameters before starting identification.
- Mechanical load connected to the motor shaft during identification, preventing accurate measurement of motor inductance and resistance.
- Faulty motor windings or internal short circuits, causing anomalous electrical characteristics during the test.
- Drive output stage fault or current measurement circuit error, leading to inaccurate readings during the identification routine.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify correct wiring of motor phases (U, V, W) to the drive output terminals. Ensure all connections are secure.
- 2
Disconnect the mechanical load from the motor shaft before initiating the automatic motor identification process.
- 3
Double-check and re-enter all motor nameplate data (P300.00 for rated power, P301.00 for rated voltage, P302.00 for rated current, P304.00 for rated speed).
- 4
Measure motor winding resistance between phases (U-V, V-W, W-U) and compare to expected values. Check for open circuits or shorts.
- 5
If the issue persists, attempt a manual motor parameter entry if possible, or contact technical support for drive diagnostics.