Übersetzen...
65290

Motor phase failure phase U

Lenze · i550 Protec Drive

Was bedeutet 65290 ?

A failure specifically of motor phase U has been detected. This indicates an open circuit in the wiring for phase U between the inverter and the motor, or an issue within the motor's U-phase winding. The error can only be reset after a 2-second blocking time.

Häufige Ursachen

  • Broken conductor in motor cable phase U between the inverter output (U) and motor terminal (U1).
  • Loose electrical connection at inverter output terminal U or motor terminal U1.
  • Internal open circuit in the motor's U-phase winding.
  • Failure of the inverter's internal power switching device (IGBT) responsible for phase U output.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    De-energize the drive and lock out power at the main disconnect.

  2. 2

    Disconnect the motor cable from the inverter's U, V, W output terminals.

  3. 3

    Measure the resistance between inverter output terminals U and V, and U and W using a multimeter; expect infinite resistance (open circuit).

  4. 4

    Measure the resistance of the motor's U-phase winding by disconnecting the motor cable from the motor and measuring between motor terminals U1-V1, U1-W1, and V1-W1; verify balanced, low resistance readings.

  5. 5

    Check for continuity of the motor cable conductor for phase U using a multimeter, measuring between the inverter-side U conductor and the motor-side U1 conductor.

Alle Codes in diesem Handbuch durchsuchen (52)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes