CMAL alarm (Pulsecoder Abnormality)
Fanuc · R-30iB Mate + Mate Plus Robot
Was bedeutet SRVO-073 ?
This alarm (Group:i Axis:j) indicates that the Pulsecoder is likely abnormal or has malfunctioned due to electrical noise. This can lead to incorrect or unstable position feedback for the associated axis, causing control instability or position errors.
Häufige Ursachen
- Pulsecoder communication anomaly (CMAL - Communication Abnormality).
- Data transfer errors between the pulsecoder and servo controller.
- Noise or interference affecting pulsecoder signals.
- Faulty pulsecoder unit or servo drive communication interface.
- Incorrect communication protocol settings or timing.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check whether the connection of the controller earth is good, verifying the earth cable connection between the controller and robot connection cables securely to the grounding plate.
- 2
Reinforce the earth of the motor flange (in case of Auxiliary axis).
- 3
Reset the Pulse count for the affected axis.
- 4
Replace the Pulsecoder for the affected axis.
- 5
Replace the robot connection cable (RMP1, RM1, RP1) connected to the affected axis.
- 6
Replace the internal cable of the robot for the Pulsecoder or motor of the affected axis.