Übersetzen...
08

Regeneration Excess Alarm

Fanuc · Alpha i Series AC Servo Motor and Spindle

Was bedeutet 08 ?

This alarm may be generated in the αi PSR when the spindle decelerates, particularly if a regenerative discharge unit with a resistance of 16Ω is used with a spindle motor having a maximum output of 5 kW or more. This indicates that the unit is not effectively dissipating regenerative energy.

Häufige Ursachen

  • Excessive regenerative energy during deceleration exceeds system limits.
  • Regenerative braking torque too high for controller's capacity.
  • Parameter settings for regeneration threshold (e.g., P3-01) are too low.
  • Faulty regenerative braking resistor system unable to dissipate excess energy.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the maximum output of the spindle motor. If it is 5 kW or more, proceed to the next step.

  2. 2

    Check the resistance of the installed regenerative discharge unit. If it is 16Ω, replace it with an 8Ω regenerative discharge unit.

Alle Codes in diesem Handbuch durchsuchen (29)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Fanuc Alpha i Series AC Servo Motor and Spindle