Übersetzen...
Diag 2 Flash 2

Error at Output 2

Beckhoff · EL2904 TwinSAFE Fail-Safe Output Terminal

Was bedeutet Diag 2 Flash 2 ?

An error has occurred specifically at digital output 2. This can be caused by faulty test pulses (due to external supply or cross-circuit), high capacitive coupling from parallel cables, an actuator current outside the 20 mA to 500 mA range, or a short-circuit/voltage drop at the output. If left unresolved, output 2 may not function safely or correctly, potentially affecting the connected safety function.

Häufige Ursachen

  • Cross-circuit fault on digital output terminal 2 (DO2) due to external voltage supply or short to another signal line.
  • Excessive capacitive coupling between output cable for DO2 and adjacent high-frequency or power cables, causing phantom signals.
  • Overcurrent condition on DO2 due to a short-circuited actuator or an overloaded load connected to the output.
  • Internal short-circuit or component failure within the digital output module's DO2 channel.
  • Faulty or inadequate test pulse monitoring on DO2, possibly due to incorrect load impedance or external interference.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Disconnect the load from digital output terminal 2 (DO2). Measure voltage between DO2 and common (0V) with a multimeter to verify no spurious voltage present.

  2. 2

    2. With power off, use an insulation tester (megger) to test the insulation resistance of the DO2 cable against ground and adjacent cables; resistance should exceed 1MΩ.

  3. 3

    3. Disconnect DO2 cable from the load. Connect a known good resistive load (e.g., 24VDC lamp) of appropriate rating to DO2. Command DO2 on/off and verify proper operation and voltage levels (e.g., 24VDC) at the load.

  4. 4

    4. Verify parameter settings for DO2 test pulse configuration (e.g., P3-14 for duration, P3-15 for frequency) are appropriate for the connected load type.

  5. 5

    5. Replace the digital output module if internal diagnostic tests indicate persistent failure on DO2 even with no load and good wiring.

Alle Codes in diesem Handbuch durchsuchen (11)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Beckhoff EL2904 TwinSAFE Fail-Safe Output Terminal