Diag 2 Flash 1

Error at Output 1

Beckhoff · EL2904 TwinSAFE Fail-Safe Output Terminal

Was bedeutet Diag 2 Flash 1 ?

An error has occurred specifically at digital output 1. This can be caused by faulty test pulses (due to external supply or cross-circuit), high capacitive coupling from parallel cables, an actuator current outside the 20 mA to 500 mA range, or a short-circuit/voltage drop at the output. If left unresolved, output 1 may not function safely or correctly, potentially affecting the connected safety function.

Häufige Ursachen

  • Cross-circuit fault on digital output terminal 1 (DO1) due to external voltage supply or short to another signal line.
  • Excessive capacitive coupling between output cable for DO1 and adjacent high-frequency or power cables, causing phantom signals.
  • Overcurrent condition on DO1 due to a short-circuited actuator or an overloaded load connected to the output.
  • Internal short-circuit or component failure within the digital output module's DO1 channel.
  • Faulty or inadequate test pulse monitoring on DO1, possibly due to incorrect load impedance or external interference.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Disconnect the load from digital output terminal 1 (DO1). Measure voltage between DO1 and common (0V) with a multimeter to verify no spurious voltage present.

  2. 2

    2. With power off, use an insulation tester (megger) to test the insulation resistance of the DO1 cable against ground and adjacent cables; resistance should exceed 1MΩ.

  3. 3

    3. Disconnect DO1 cable from the load. Connect a known good resistive load (e.g., 24VDC lamp) of appropriate rating to DO1. Command DO1 on/off and verify proper operation and voltage levels (e.g., 24VDC) at the load.

  4. 4

    4. Verify parameter settings for DO1 test pulse configuration (e.g., P3-12 for duration, P3-13 for frequency) are appropriate for the connected load type.

  5. 5

    5. Replace the digital output module if internal diagnostic tests indicate persistent failure on DO1 even with no load and good wiring.