Übersetzen...
0022
WATCHDOG TIMER EXPIRED, SEE S:3
Allen-Bradley · MicroLogix 1400 Programmable Controllers
Was bedeutet 0022 ?
The program scan time exceeded the configured watchdog timeout value, which is stored in status file S:3H. This is a nonrecoverable fault, indicating that the controller's program took too long to execute, potentially due to an infinite loop, excessive processing, or an incorrectly set watchdog timer.
Häufige Ursachen
- Program logic is caught in an infinite or excessively long loop.
- Excessive processing load due to complex calculations or communication tasks during a single scan.
- Watchdog timeout value in status file S:3H is set too low for the program's complexity and execution time.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Review the program logic to identify and correct any infinite loops or sections that take an extended time to execute.
- 2
Increase the watchdog timeout value in status file S:3H, but ensure it remains appropriate for the application's safety and response time requirements.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Allen-Bradley MicroLogix 1400 Programmable Controllers