Übersetzen...
-1

Output Error

Allen-Bradley · MicroLogix 1400 Programmable Controllers

Was bedeutet -1 ?

An invalid output has been specified for a PTOX instruction. Only Output 2, Output 3, and Output 4 are valid choices. This is a configuration error that causes the controller to fault, and the User Fault Routine does not execute.

Häufige Ursachen

  • PTOX instruction configured to use an output other than the valid Output 2, Output 3, or Output 4.
  • Typographical error or incorrect address assignment in the output parameter of the PTOX instruction.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the PTOX instruction is configured to use a valid physical output (Output 2, Output 3, or Output 4).

  2. 2

    Correct the output address specified in the PTOX instruction within the ladder program to one of the valid options.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Allen-Bradley MicroLogix 1400 Programmable Controllers