Übersetzen...
5300

PANEL LOSS

ABB · ACS800

Was bedeutet 5300 ?

Communication with the control panel, which is currently selected as the active control location for the ABB ACS800 drive, has been lost. This fault (3.09 AW 2 bit 13) can lead to a loss of control and monitoring capabilities from the panel, and its behavior is governed by programmable Fault Function 30.02 (PANEL LOSS).

Häufige Ursachen

  • Loose or faulty physical connection of the control panel to the drive.
  • Damage to the control panel itself or its mounting platform/connector.
  • Malfunction of the control panel's internal electronics.
  • Incorrect setting of Fault Function parameter 30.02 (PANEL LOSS) which dictates the drive's reaction to communication loss.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check the physical connection of the control panel to the ABB ACS800 drive, ensuring it is securely seated in its mounting platform and latches are engaged.

  2. 2

    Inspect the control panel connector and the corresponding receptacle on the drive for any visible damage, bent pins, or corrosion.

  3. 3

    If possible, test with a known good control panel by temporarily replacing the existing panel in the mounting platform.

  4. 4

    Verify parameter 30.02 (PANEL LOSS) settings to ensure the desired drive reaction (FAULT, CONST SP 15, LAST SPEED) is selected for a panel communication break.

  5. 5

    Refer to the appropriate ABB ACS800 hardware manual for detailed instructions on panel connection and troubleshooting procedures.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes