Übersetzen...
3210

DC OVERVOLT

ABB · ACS800

Was bedeutet 3210 ?

Excessive intermediate circuit DC voltage has been detected in the ABB ACS800 drive. The DC overvoltage trip limit is calculated as 1.3 × 1.35 × U1max, where U1max is the maximum supply voltage. For a 400V unit (U1max = 415V), the trip level is 728V DC; for 500V units (U1max = 500V), it's 877V DC; and for 690V units (U1max = 690V), it's 1210V DC.

Häufige Ursachen

  • Regenerative energy from the motor during deceleration, especially with high inertia loads or short deceleration times.
  • Static overvoltage or transient voltage spikes on the main supply line.
  • Malfunction or incorrect sizing of the brake chopper and brake resistor (if installed).
  • Deceleration time parameter set too short for the application's inertia.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check that the overvoltage controller is enabled (Parameter 20.05).

  2. 2

    Check the supply voltage for static or transient overvoltage conditions using a multimeter or power quality analyzer.

  3. 3

    If used, check the brake chopper and brake resistor for proper operation, sizing, and connections.

  4. 4

    Increase the deceleration time (e.g., parameter 22.03) to allow for a slower stop, reducing regenerative energy.

  5. 5

    Consider implementing a coast-to-stop function (if applicable) to allow the motor to freewheel to a stop.

  6. 6

    Retrofit the frequency converter with a brake chopper and brake resistor if not already present and necessary for the application to dissipate regenerative energy.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes