8

DC under voltage

Danfoss · VLT HVAC Drive FC 102

What does 8 mean?

If the intermediate circuit voltage (DC link) drops below the under-voltage limit, the frequency converter checks for a 24 V DC back-up supply. If no back-up is connected, the unit trips after a fixed delay. This condition can lead to unexpected shutdowns and loss of motor control.

Common Causes

  • Significant voltage sag or complete loss of one or more phases in the incoming AC mains supply.
  • Tripped upstream circuit breaker or blown fuses on the drive's input power lines (L1, L2, L3).
  • Loose or high-resistance connections at the drive's input terminals, leading to voltage drop under load.
  • Absence of a 24VDC backup supply connection to terminals 12/13 when required during a main power loss event.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the incoming AC mains voltage at terminals L1, L2, L3 to verify it remains above the minimum specified operating voltage during operation.

  2. 2

    Inspect all fuses and circuit breakers in the supply path to the drive; replace blown fuses or reset tripped breakers.

  3. 3

    Tighten all power wiring connections at the drive's input terminals (L1, L2, L3) and inspect for signs of arcing or corrosion.

  4. 4

    If 24VDC backup is used, verify the backup supply voltage at terminals 12 and 13, and check its current capacity against drive requirements.

Browse all codes in this manual (75)
Verified technical data. Last updated: March 2026

Related Faults

Source: Danfoss VLT HVAC Drive FC 102