Line side unit warning
ABB · ACS880
What does AF85 mean?
The supply unit (or another converter) has generated a warning. The auxiliary code specifies the original warning code from the supply unit's control program. This indicates a problem on the line-side of the system, which could affect the entire drive operation.
Common Causes
- A specific warning condition (e.g., over-temperature, supply undervoltage) has occurred within the line-side unit (LSU), generating a local warning.
- Auxiliary code indicates a temporary issue on the AC supply network connected to the LSU, such as a phase imbalance or voltage sag (e.g., 'A500: Mains undervoltage').
- Control parameter in the LSU (e.g., P3-10: Mains supervision level) is set too sensitively, triggering warnings during normal operating transients.
- An external device connected to the LSU's inputs (e.g., cooling fan status) has triggered a warning in the LSU's control program.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Access the control panel or diagnostic interface of the line-side unit (LSU) and retrieve the specific warning code (auxiliary code) that triggered AF85.
- 2
Investigate the specific LSU warning code obtained in step 1 using the LSU's documentation to understand its root cause.
- 3
Monitor the incoming AC mains voltage and frequency at the LSU's input terminals (e.g., L1, L2, L3) for stability and compare against nominal values.
- 4
Verify the LSU's internal temperature sensors via diagnostic readouts to check for localized overheating.
- 5
Review the LSU's parameters, specifically those related to mains supervision (e.g., P3-10) and external input warnings, for appropriate settings.