E2-2

Internal PROFIsafe Initialization/Operation Error

ABB · AC500-S Safety Controller

What does E2-2 mean?

The SM560-S Safety PLC has encountered a fundamental internal error during PROFIsafe initialization or general PROFIsafe operation. This critical fault indicates a problem with the safety communication stack, preventing safe operation.

Common Causes

  • Corrupted PROFIsafe stack or firmware within the SM560-S Safety PLC during boot-up or runtime, preventing proper safety communication.
  • Internal hardware failure within the SM560-S Safety PLC affecting its PROFIsafe communication controller or internal bus system.
  • Incorrect or incompatible PROFIsafe configuration loaded into the Safety PLC, preventing proper initialization of the safety communication parameters.
  • Severe electromagnetic interference (EMI) disrupting the internal communication buses or processor of the SM560-S PLC during PROFIsafe operations.
  • Critical operating system error within the SM560-S Safety PLC impacting its ability to manage safety-critical tasks and PROFIsafe protocols.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Perform a power cycle of the entire SM560-S Safety PLC and observe if the internal PROFIsafe error clears upon restart.

  2. 2

    2. Connect to the Safety PLC via engineering software and perform a complete re-download of the boot project and the safety application to the device.

  3. 3

    3. Verify the integrity of the PROFIsafe configuration parameters for all connected safety devices within the engineering software (e.g., F_Source_Address, F_Dest_Address, F_iPar_CRC).

  4. 4

    4. Check the PLC's diagnostic buffer via the engineering software for more detailed sub-codes or contextual error messages related to the PROFIsafe initialization failure.

  5. 5

    5. If the error persists after all software and power checks, replace the SM560-S Safety PLC CPU module with a known good spare and re-download the safety application.

Browse all codes in this manual (48)
Verified technical data. Last updated: March 2026

Related Faults

Source: ABB AC500-S Safety Controller