E2-10
Internal Error (SM560-S)
ABB · AC500-S Safety Controller
What does E2-10 mean?
The SM560-S Safety PLC has encountered an unspecified internal error. This indicates a system malfunction that prevents normal operation and requires intervention.
Common Causes
- Unspecified internal hardware fault within the SM560-S module, potentially transient.
- Corruption of the operating system firmware after a power event.
- Temporary internal bus error due to electromagnetic interference (EMI).
- Software deadlock or exception within the Safety PLC's internal processes.
- Overheating of the SM560-S module due to inadequate ventilation in the control cabinet.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Perform a power cycle of the SM560-S module (turn 24VDC supply off for 10 seconds, then on).
- 2
2. Inspect the installation environment for excessive vibration or strong electromagnetic fields (EMI sources) near the PLC.
- 3
3. Verify the event log in the engineering software for specific internal sub-codes or associated error messages.
- 4
4. Re-download the current application program and firmware to the SM560-S module.
- 5
5. Replace the SM560-S Safety PLC module if the internal error persists after these steps.
Verified technical data. Last updated: March 2026
Related Faults
Source: ABB AC500-S Safety Controller