oPE05
Option Board Missing / Pulse Input Conflict
Yaskawa · V1000 AC Drive
What does oPE05 mean?
This error occurs either when the run command source (b1-02) or frequency reference source (b1-01) is set to an option board (value 3) that is not physically installed, or when the frequency reference source is set to pulse input but H6-01 is not set to 0. This indicates a conflict in the drive's control source configuration.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If using pulse input as a frequency reference, ensure parameter H6-01 is correctly set to 0 to enable this function.
Source: Yaskawa V1000 AC Drive