CE

Communication Data Error

Yaskawa · GA500 Maintenance and Troubleshooting

What does CE mean?

This fault indicates that the drive has experienced a communication data error, typically due to electrical interference on the control circuit lines. The drive detects this error if it fails to receive correct control data within the timeout period defined by parameter H5-09. If left unaddressed, this can lead to unreliable control of the motor, unexpected stops, or incorrect operation, potentially disrupting the process.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Use only recommended shielded cables and ground the shield on the controller side or the drive input power side.

  2. 4

    Separate communication wiring from drive power lines and install a noise filter on the input side of the power supply for communication.

  3. 5

    Decrease the effects of electrical interference originating from the controller itself. After addressing the cause, perform a Fault Reset.

Source: Yaskawa GA500 Maintenance and Troubleshooting