OH
Heatsink Overheat
Yaskawa · F7 Drive
What does OH mean?
The temperature of the Drive's heatsink has exceeded the programmed setpoint (L8-02, L8-03=0 to 2), indicating inadequate cooling or excessive ambient temperature. This can be caused by a nearby heat source, dirt buildup on fans/heatsink, or high room temperature. Persistent overheating will lead to nuisance trips, reduced performance, and can significantly shorten the Drive's lifespan.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Ensure there is adequate ventilation around the Drive, and that no external heat sources are impinging on its cooling surfaces.
- 4
Verify the settings for heatsink overheat detection (L8-02 and L8-03) are appropriate for the application and operating environment.
Source: Yaskawa F7 Drive