E-15
SI-F/G Communication Error Detected
Yaskawa · F7 Drive
What does E-15 mean?
A communication error has occurred when the SI-F/G Option Card is designated as the source for run commands or frequency reference (b1-01=3 and/or b1-02=3), and communication with it is lost. This implies a failure in the communication link or configuration with the SI-F/G card. Without proper communication, the Drive cannot receive critical commands or references, leading to a stop.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check the setting of parameter F6-01 (Communication Option Selection) to ensure it matches the installed SI-F/G card type.
- 4
Review and confirm the communication configuration on the host side (master controller) for compatibility and correct protocol settings.
Source: Yaskawa F7 Drive