PUF
DC Bus Fuse Open
Yaskawa · E7 Drive
What does PUF mean?
The Drive detects that the DC bus fuse has opened. This is typically caused by shorted output transistor(s) or output terminals, indicating a severe internal fault in the power circuit. The fuse opens to protect upstream components but requires addressing the underlying short.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Perform internal checks (referencing Table 6.6, if available, or standard procedures) without power to identify shorted components.
- 4
Replace any identified shorted component(s), such as output transistors.
- 5
Replace the defective DC bus fuse with one of the correct rating.