Option PCB Communication Error Fault
Yaskawa · E7 Drive
What does F6-CEF mean?
This fault occurs when a serial communication option board, attached to the drive at the 2CN connector, detects a communication error. Unless parameter F6-01 is specifically set to '3: Alarm Only', this condition will energize the fault output and potentially stop the drive, indicating a critical problem with the communication link to the option board.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check the communication parameters (e.g., baud rate, parity, address) configured on both the option board and the external master for consistency.
- 4
If F6-01 is not set to '3: Alarm Only', try setting it temporarily to 'Alarm Only' to observe if the communication issue persists as an alarm rather than a fault, which can aid in diagnosis.
- 5
Consult the specific option board manual for diagnostic indicators, LEDs, or communication status registers for more detailed error information.