Vacon 100 FLOW

73 fault codes documented

1

Overcurrent

The frequency converter has detected a motor current exceeding 4 times the nominal current (I_H). This condition can result from a sudden heavy load increase, a short circuit in the motor cables, or an unsuitable motor for the drive. Subcodes indicate hardware trip, current cutter, or current controller supervision.

2

Overvoltage

The DC-link voltage has exceeded its predefined limits. Common causes include a deceleration time setting that is too short, or high overvoltage spikes present in the incoming supply voltage. Subcodes specify if it's a hardware trip or overvoltage control supervision.

3

Earth fault

Current measurement has detected that the sum of the motor phase currents is not zero. This indicates an insulation failure in the motor cables or within the motor windings themselves, causing current to flow to ground.

5

Charging Switch Malfunction

The internal charging switch is commanded to close, but its feedback indicates it is still open, suggesting an operational malfunction or a defective component. This prevents the DC link from being properly charged, inhibiting drive startup or operation. If ignored, the drive will not function.

6

Emergency stop

A stop signal has been received from an option board, indicating that an external emergency stop circuit has been activated. This typically means an external safety device or system has initiated a shutdown.

7

Saturation trip

This fault has various potential causes, including a defective internal component or a short-circuit or overload in the brake resistor. This fault cannot be reset from the keypad and requires immediate power attention.

8

System Fault

This broad fault indicates various internal drive malfunctions, including lack of communication between control and power boards, defective components (e.g., control board), low auxiliary power voltage, output phase voltage disagreement with reference, software incompatibility between units, unreadable software versions, resource overload, or CPU overload. These issues compromise the drive's operational integrity and can lead to unpredictable behavior.

9

Undervoltage

The DC-link voltage has fallen below the voltage limits defined in Table 37. The most probable cause is a supply voltage that is too low, or an internal frequency converter fault. Subcodes specify if the DC-link was too low during run, no data from power unit, or undervoltage control supervision.

10

Input line supervision

One of the input line phases is missing. This detection can be via phase supervision diode supply or an active front end. This usually points to an issue with the incoming power supply or its connection.

11

Output phase supervision

Current measurement has detected that there is no current flowing in one of the motor phases. This indicates a break in the circuit to the motor, either in the motor cable itself or within the motor windings.

12

Brake chopper supervision

This fault indicates that either no brake resistor is installed, the installed brake resistor is broken, or there is a failure within the brake chopper unit itself. This prevents proper dissipation of regenerative energy.

13

Frequency converter undertemperature

The heatsink temperature of the frequency converter is measured to be below –10°C. This indicates an unusually cold ambient operating environment.

14

Frequency converter overtemperature

The heatsink temperature of the frequency converter has exceeded 90°C, after a warning issued at 85°C. Subcodes indicate if the measurement itself or an internal thermistor is the source of the detection. This suggests insufficient cooling or excessive internal heat generation.

15

Motor stalled

The motor stall protection has tripped. This occurs when the motor is unable to rotate or maintain speed under load, possibly due to a mechanical obstruction, excessive load, or insufficient motor torque.

16

Motor Overtemperature

The motor has exceeded its safe operating temperature, often indicating that the load applied to the motor is too heavy for its current capabilities. If the load is not excessive, the motor's thermal protection parameters in the drive may be incorrectly configured. Sustained motor overtemperature can degrade winding insulation, leading to premature motor failure.

17

Motor Underload

The motor is operating with insufficient load, meaning the actual load is below the expected or minimum threshold. This can occur if the mechanical load is unexpectedly disconnected or too light, or if drive parameters related to load monitoring are incorrectly set. While less critical than overload, persistent underload can indicate a process issue or inefficiency.

18

Unbalance

This is a warning (not a fault trip) indicating an unbalance between power modules in paralleled units. Subcodes specify if the unbalance is in current or DC-Voltage.

19

Drive Short-Time Power Overload

The drive has detected an excessive power demand that is too high for its specified rating over a short duration. This suggests that the drive itself may be undersized for the connected motor and load, or the current load is momentarily exceeding its capabilities. Repeated short-time overloads can lead to drive component stress and eventual failure.

22

EEPROM checksum fault

A parameter save fault has occurred, indicating an issue with storing data to or retrieving data from the EEPROM. This can be due to faulty operation or a component failure within the EEPROM memory.

24

Counter fault

The values displayed on the frequency converter's internal counters are incorrect. This suggests an issue with the internal counting mechanism or data integrity.

25

Motor Control Fault

This fault, specific to customer-specific applications, indicates a malfunction during the start angle identification process. Possible causes include rotor movement during identification or a mismatch between the new and old angle values. This prevents accurate motor control and startup.

26

Startup Prevented

The drive cannot perform a startup because a new software (firmware or application), parameter setting, or other file affecting operation was loaded while a Run request was ON. The drive prevents startup to ensure configuration integrity and prevent improper operation.

29

Thermistor fault

The thermistor input on an option board has detected too high a motor temperature, or the input itself is improperly terminated. This protects the motor from overheating.

30

Safety System Fault

This fault encompasses diverse issues related to the drive's safety functions. It can be triggered by an active Safe Off signal preventing drive readiness, incorrect safety configuration (e.g., wrong safety switch installation, incorrect STO board placement or count, incompatibility), safety diagnostics failures (e.g., STO input status mismatch, ATEX thermistor connection issues or short circuits), or the activation of the Safe Torque Off (STO) function itself (e.g., via emergency stop). These faults indicate a compromise in the drive's ability to maintain a safe operating state and require careful investigation.

31

IGBT temperature (hardware)

The IGBT Inverter Bridge hardware overtemperature protection has detected an excessively high short-term overload current. This typically occurs under heavy transient loads or with incorrect motor sizing.

32

Fan cooling

The cooling fan of the frequency converter does not start when an ON command is given. This will lead to insufficient cooling and potential overtemperature conditions.

33

Fire Mode Enabled

The drive's Fire mode is currently enabled, which intentionally disables certain drive protections to ensure continuous operation in emergency situations. This is an informational alarm indicating a specific operational state, and it resets automatically when Fire mode is disabled.

34

CAN bus communication

A message sent on the CAN bus was not acknowledged, indicating a communication issue. This could be due to an inactive device on the bus or a mismatch in configuration.

35

Application problem

A problem has occurred within the application software running on the frequency converter. This indicates an issue with the custom programming or logic.

37

Device changed (same type)

An option board or power unit has been changed to a new device of the same type and rating. Old parameter settings will continue to be used.

38

Device added (same type)

An option board of the same type has been added to the frequency converter. The existing board settings will be used.

39

Option Board Removed (Slot A/B)

An option board previously configured for slot A or B has been physically removed from the drive. This means the functionality provided by that specific option board is no longer available. This condition will persist until acknowledged or corrected.

40

Unknown Device Connected

The drive has detected an unknown device connected to one of its slots, such as an unrecognized power unit or option board. The drive cannot identify or utilize this device, rendering its functionality unavailable. This can lead to system instability or prevent expected operations.

41

IGBT temperature

The IGBT Inverter Bridge overtemperature protection has detected an excessively high short-term overload current. This typically occurs under heavy transient loads or with incorrect motor sizing.

42

Brake resistor overtemperature

The brake resistor has exceeded its safe operating temperature limit. This indicates that the resistor is dissipating too much energy, possibly due to excessive braking, incorrect resistance value, or insufficient cooling.

43

Encoder fault

A problem has been detected in the encoder signals. Subcodes pinpoint specific issues such as missing channel A or B signals, both channels missing, encoder reversed, missing encoder board, serial communication fault, channel A/B mismatch, resolver/motor pole pair mismatch, or missed start angle.

44

Device changed (different type)

An option board or power unit has been changed to a new device of a different type or rating than the previously installed one. This requires parameter re-configuration for the new device.

45

Device Added (Different Type)

A new power unit or option board (in slot C, D, or E) of a *different type* has been added or detected in the drive. Similar to 'Device changed (different type),' this means parameters for the new device are not saved or compatible, requiring initial configuration. Without proper setup, the added device will not function correctly.

46

Real Time Clock Battery Low

The voltage of the Real Time Clock (RTC) battery is low, indicating it needs replacement. A low RTC battery can lead to loss of time and date settings upon power cycle, affecting data logging and time-dependent functions.

47

Software Updated

The drive's software (full package or an application) has been successfully updated. This is an informational message and not an error or fault requiring troubleshooting. It confirms the successful completion of a software upgrade.

49

Division by zero in application

A division by zero error has occurred within the application program running on the frequency converter. This indicates a mathematical error in the custom logic.

50

Analog Input Current Low

The current at an analogue input, configured for a 4-20 mA signal range, is measured to be below 4 mA. This typically indicates a broken or loose control cable or a failure of the signal source providing the current.

51

Device External Fault

A user-specified digital input signal (configured with parameter P3.5.1.11 or P3.5.1.12) was activated, triggering an external fault. This indicates an issue with an external device or its signaling to the drive, which is configured to stop the drive upon activation.

52

Keypad Communication Fault

The connection between the control panel (keypad) and the drive is defective, preventing proper communication. This could be due to a faulty cable, improper seating of the keypad, or a damaged control panel itself. Loss of communication means the drive cannot be controlled or monitored via the keypad.

53

Fieldbus Communication Fault

The data connection between the fieldbus master and the fieldbus board in the drive is defective. This prevents the drive from receiving or sending data via the fieldbus network, disrupting remote control and monitoring. Prolonged communication loss can lead to process control issues.

54

Slot Fault

A defective option board or slot has been detected in one of the drive's expansion slots (A, B, C, D, or E). This indicates a hardware issue with an installed option board or its physical slot on the control unit. Such faults can disable functionality provided by the option board or prevent drive operation.

56

PT100 board temperature fault

The temperature limit values set for the PT100 option board parameters have been exceeded. This indicates an overtemperature condition on the PT100 board itself or its connected sensors.

57

Identification Run Failure

The motor identification run failed to complete successfully. This can occur if the motor is not properly connected, if there's mechanical load on the shaft during the run, or if the start command is prematurely removed. An incomplete identification run means the drive may not have optimal motor parameters.

63

Quick Stop Fault

The Quick Stop function has been activated, causing the drive to stop rapidly. This fault indicates an intentional or unintentional triggering of the quick stop safety feature, designed to bring the motor to a halt quickly. Understanding its activation source is crucial to prevent unintended stops.

65

PC Communication Fault

The data connection between the PC and the drive is defective, preventing communication with PC tools (e.g., commissioning software). This can be caused by faulty cabling, incorrect terminal connections, or installation issues. Without this connection, advanced configuration and diagnostics are not possible.

66

Thermistor Input Fault

The motor temperature has increased beyond limits, as detected by a thermistor input, or there is an issue with the thermistor circuit itself. This could be due to inadequate motor cooling, excessive mechanical load on the motor, or a faulty thermistor connection. Overtemperature can lead to motor damage and reduced lifespan.

68

Maintenance Counter 1 Alarm

Maintenance counter 1 has exceeded its programmed alarm limit, indicating that scheduled maintenance is due or overdue for the component it monitors. This is an advisory alarm to prompt proactive maintenance activities. Ignoring this alarm could lead to component wear, reduced performance, or unexpected faults.

69

Fieldbus Communication Fault

This fault indicates an issue with fieldbus communication, specifically that an invalid ID number is being used for mapping values to Fieldbus Process Data Out. This prevents correct data exchange between the drive and the fieldbus master, leading to control issues or loss of monitoring.

76

Start Prevented

The drive's start command has been blocked, primarily to prevent accidental motor rotation, especially during the initial power-up sequence. This is a safety feature to ensure the system is in a known, safe state before operation. The drive will not operate until this prevention is cleared.

77

Too Many Active Connections

The drive has detected more than 5 active fieldbus or PC tool connections simultaneously. The system limits concurrent connections to a maximum of 5. Exceeding this limit can cause communication instability or prevent new connections.

101

PID Feedback Supervision Fault (PID1)

The feedback value for PID controller 1 is outside the configured supervision limits (P3.13.6.2 and P3.13.6.3) for a specified delay (P3.13.6.4). This indicates a deviation from the expected process variable feedback, suggesting an issue with the process or the sensor. It can lead to incorrect control actions and process instability.

105

External PID Feedback Supervision Fault

The feedback value for the external PID controller is outside its configured supervision limits (P3.14.4.2 and P3.14.4.3) for a specified delay (P3.14.4.4). This indicates a problem with the external process feedback, potentially leading to unstable control or incorrect process regulation. It signifies a deviation in the external process variable.

109

Input Pressure Supervision Fault

The input pressure supervision signal (P3.13.9.2) has dropped below either the alarm limit (ID 1109) or the fault limit (ID 1409), indicating an issue with the system's input pressure. This could affect pump or process operation, potentially leading to cavitation, poor performance, or system shutdown.

111

Temperature Fault 1

One or more temperature input signals (configured in P3.9.6.1) have exceeded the alarm limit (P3.9.6.2) or the fault limit (P3.9.6.3). This indicates an overtemperature condition in a monitored area or a problem with the temperature sensing circuit. Unresolved overtemperature can lead to equipment damage.

112

Temperature Fault 2

One or more temperature input signals (configured in P3.9.6.5) have exceeded the alarm limit (P3.9.6.6) or the fault limit (P3.9.6.7). This signifies an overtemperature condition in a second monitored area or an issue with the second set of temperature sensing inputs. Ignoring this can lead to critical component failure.

113

Pump Running Time Limit Exceeded

In a Multipump system, one or more pump running time counters have exceeded a user-specified alarm or fault limit. This indicates that a pump has reached its programmed maintenance interval or has been operating for an excessively long period without intervention. Timely maintenance prevents wear and premature failure.

131

AC Drive Heatsink Overtemperature Alarm

The temperature of the power unit's heatsink has reached an elevated level, triggering an alarm, indicating it is approaching the fault limit. This could be due to inadequate cooling, dusty heatsink, high ambient temperature, excessive switching frequency, or a failing cooling fan. While not yet a fault, sustained high temperatures will reduce component lifespan and may lead to a fault trip.

132

AC Drive Board Overtemperature Fault

The temperature on the AC drive's power board has exceeded its safe operating limit, indicating a critical overheating condition. This fault is typically caused by insufficient cooling air, high ambient temperatures, or internal component issues. Sustained high temperatures on the board can lead to permanent damage to sensitive electronic components.

133

AC Drive Board Overtemperature Alarm

The temperature on the AC drive's power board has reached an elevated level, triggering an alarm before reaching a critical fault condition. This indicates that the board's temperature is approaching its fault limit, likely due to insufficient cooling or high ambient temperatures. Although not yet a fault, continuous operation under these conditions can lead to component degradation and eventual fault tripping.

181

Drive Long-Time Power Overload

The drive has experienced a sustained power demand that continuously exceeds its rated capacity over an extended period. This condition signifies that the drive is consistently undersized for the application's demands, leading to thermal stress on its power components. Persistent long-time overloads will severely shorten the drive's operational life and lead to component failure.

383

Option Board Removed (Slot C)

An option board configured for slot C has been physically removed from the drive. This indicates that the functionalities provided by this option board are now unavailable. The drive will register this as an error until the issue is addressed.

384

Option Board Removed (Slot D)

An option board previously installed in slot D has been detected as removed from the drive. The functionalities associated with this specific option board are no longer accessible. This fault requires attention to either acknowledge the removal or reinstall the board.

385

Option Board Removed (Slot E)

An option board that was configured for slot E has been physically removed from the drive. This means any features or connections provided by this option board are currently inactive. This fault will remain until appropriate action is taken.

1302

Maintenance Counter 1 Fault

Maintenance counter 1 has exceeded its programmed fault limit, which is typically higher than the alarm limit. This indicates that a critical maintenance interval has been significantly surpassed, potentially impacting equipment reliability or safety. This fault requires immediate attention to prevent operational issues.

1303

Maintenance Counter 2 Alarm

Maintenance counter 2 has exceeded its programmed alarm limit, serving as an advisory to schedule or perform maintenance for the component it monitors. This is a pre-warning before a potential fault condition. Proactive maintenance is crucial to maintain optimal equipment performance and prevent unexpected downtime.

1304

Maintenance Counter 2 Fault

Maintenance counter 2 has exceeded its programmed fault limit, indicating that the maintenance interval for the monitored component has been critically overdue. This fault state demands immediate action as continued operation without maintenance could compromise equipment integrity or lead to system failures.

1311

Fieldbus Process Data Out Conversion Error

The drive is unable to convert one or more values for Fieldbus Process Data Out because the data type is not correctly specified or incompatible. This prevents the drive from accurately transmitting process data over the fieldbus. Incorrect data types can lead to misinterpretation by the fieldbus master and potential control anomalies.

1312

Fieldbus Process Data Out Overflow (16-bit)

An overflow has occurred during the mapping and conversion of values for Fieldbus Process Data Out (specifically 16-bit values). This means that a value being transmitted is too large to be represented accurately within a 16-bit data format, leading to truncation or incorrect data. This can result in inaccurate control or monitoring feedback.