43
Encoder fault
Vacon · NXP/C AC Drive
What does 43 mean?
A problem has been detected in the encoder signals, which are crucial for speed and position control. Subcodes in T.14 provide specifics like missing channels A (S1) or B (S2), both channels missing (S3), reversed encoder (S4), missing encoder board (S5), serial communication fault (S6), channel A/B mismatch (S7), resolver/motor pole pair mismatch (S8), or missed start angle (S9). This can lead to loss of accurate motor control.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Ensure the encoder wiring shield is properly grounded to prevent electrical noise and signal interference.
Source: Vacon NXP/C AC Drive