240001

Fault at DRIVE-CLiQ socket X101

Siemens · SINUMERIK 828D

What does 240001 mean?

This fault indicates that an issue has occurred at the drive object connected to DRIVE-CLiQ socket X101. The fault value (r0949) specifies the first fault that manifested for this particular drive object, providing a pointer to the specific problem. This general fault suggests a problem within the DRIVE-CLiQ communication or the connected component, potentially leading to loss of control or communication with the associated drive component if not addressed.

Common Causes

  • DRIVE-CLiQ cable damage (e.g., crushing, insulation degradation) between the control unit and the drive object connected to X101.
  • Oxidation or debris on the pins of the DRIVE-CLiQ connector X101, leading to intermittent signal transmission.
  • Incorrect or missing electronic nameplate data for the component attached to X101, preventing proper communication initialization.
  • Firmware version mismatch between the main control unit and the drive component on X101.
  • Internal hardware defect within the drive object connected to X101, causing it to fail startup or operation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Note the specific fault code in parameter r0949 to diagnose the underlying issue reported by the device on X101.

  2. 2

    2. Perform a thorough visual inspection of the DRIVE-CLiQ cable routing and connections to socket X101 on both ends for any physical damage.

  3. 3

    3. Clean the contacts of the DRIVE-CLiQ connector X101 on the control unit and the corresponding connector on the drive object using contact cleaner (e.g., isopropyl alcohol).

  4. 4

    4. Use an oscilloscope to check the signal integrity on the DRIVE-CLiQ line connected to X101 if the cable passes continuity tests.

  5. 5

    5. Cross-verify the installed device at X101 against the configured device in the project software (e.g., SINAMICS DCC) for correct type and firmware.

  6. 6

    6. Attempt to cycle power to only the drive object connected to X101 to reset its internal state before cycling the entire system.

Browse all codes in this manual (37)
Verified technical data. Last updated: March 2026

Related Faults