A35416
TM150 Temperature Alarm Channel 10
Siemens · SINAMICS S120/S150 List
What does A35416 mean?
This alarm is initiated when the actual temperature (r4105[10]) for channel 10 on Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[20]). A timer (p4103[10]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[10]).
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check for any immediate causes of temperature increase for the affected component, such as temporary overloads or environmental factors.
- 4
Verify the temperature sensor operation and connection for channel 10.
- 5
Review the alarm threshold setting (p4102[20]) and hysteresis (p4118[10]) to ensure they are appropriate for the application.
Source: Siemens SINAMICS S120/S150 List