F07016
Drive: Motor temperature sensor fault
Siemens · SINAMICS G120C Variable Speed Drive
What does F07016 mean?
An error has been detected in the evaluation of the motor temperature sensor configured in p0601. This could be due to a wire breakage, the sensor being disconnected (e.g., KTY resistance > 2120 Ohm), or the measured resistance being too low (e.g., PTC resistance < 20 Ohm, KTY resistance < 50 Ohm). The fault causes an OFF1 reaction and prevents proper motor temperature monitoring, risking motor damage from overheating if not resolved.
Source: Siemens SINAMICS G120C Variable Speed Drive
View Official PDF