A30054

Power unit: Undervoltage when opening the brake

Siemens · SINAMICS G120C Variable Speed Drive

What does A30054 mean?

The power supply voltage for the brake has dropped below 21.6V (24V - 10%) when the brake is commanded to open. The alarm value (r2124) indicates the detected voltage. This undervoltage can prevent the brake from opening properly, leading to mechanical binding, potential damage to the brake mechanism, or a failure to start the motor.

Source: Siemens SINAMICS G120C Variable Speed Drive