A05004
Power unit: Rectifier overtemperature
Siemens · SINAMICS G120C Variable Speed Drive
What does A05004 mean?
The alarm threshold for the rectifier's overtemperature has been reached, indicating excessive heat generation in the input rectifier stage. This can be due to overload or cooling issues. If the rectifier temperature rises by an additional 5 K, it will trigger fault F30037, potentially causing the drive to trip and risking damage to the rectifier components.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check the cooling fan for failure and verify its direction of rotation.
- 4
Inspect the line supply for any missing phases or issues.
- 5
Check for defects in an arm of the supply (incoming) rectifier.
Source: Siemens SINAMICS G120C Variable Speed Drive