A01690

Safety parameter changed

Siemens · SINAMICS G120

What does A01690 mean?

A safety-related parameter has been modified either during safety commissioning or a safety reset. This warning is issued to ensure that all safety changes are intentionally acknowledged and finalized, as unresolved changes can prevent the drive from entering a safe operational state, potentially compromising machine safety.

Common Causes

  • A safety parameter (e.g., P0910 for STO, P0951 for SLS) was intentionally changed and requires acknowledgment via P0976.
  • Safety function block in the PLC or safety controller was reconfigured, resulting in new safety parameter values sent to the drive.
  • Drive firmware update that modifies internal safety parameter structures, requiring re-acknowledgment after the update.
  • Memory corruption within the drive causing an unintentional change in safety parameter values that needs to be reset or acknowledged.
  • Incorrect safety parameter upload from a backup file, leading to discrepancies between the stored and current values.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Review all safety-related parameters (e.g., those in the P09xx series) to identify which ones have been modified since the last acknowledgment.

  2. 2

    2. Acknowledge the safety parameter changes by setting parameter P0976 (Safety acknowledge) to the required value (e.g., 1 or 2) after verifying them.

  3. 3

    3. If safety parameters were changed via a PLC or safety controller, ensure the configuration matches the drive's expectations and then re-acknowledge.

  4. 4

    4. Perform a safety commissioning procedure as detailed in the drive's safety manual, including signature generation if applicable.

  5. 5

    5. If changes were unintentional, load the last known good safety parameter set from a backup file and then acknowledge the restore via P0976.

Browse all codes in this manual (109)
Verified technical data. Last updated: March 2026

Related Faults