A00706

PROFIBUS: fatal SW error

Siemens · SINAMICS G120

What does A00706 mean?

A fatal software error has occurred within the PROFIBUS communication module, potentially related to hardware checks, general communication issues, or problems with the V1SL stack. This critical error can lead to a complete loss of PROFIBUS connectivity and drive control, rendering the system inoperable via PROFIBUS.

Common Causes

  • Corrupted PROFIBUS GSD file loaded into the master (e.g., PLC) causing incompatible communication settings for the drive.
  • Firmware bug within the drive's PROFIBUS communication board (CB) requiring an update to a stable version.
  • Internal hardware fault on the PROFIBUS communication board preventing proper initialization or consistent operation.
  • Severe electromagnetic interference (EMI) causing data corruption during the communication module's initialization phase.
  • Incompatible PROFIBUS master or specific configuration attempting unsupported functions, leading to internal software errors.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Power cycle the drive by disconnecting and reconnecting the main supply voltage, then observe if the fault clears upon restart.

  2. 2

    2. Verify the PROFIBUS GSD file used in the master's hardware configuration is the correct and latest version for the drive's firmware revision.

  3. 3

    3. Update the drive's firmware to the latest available version, especially if known bugs related to PROFIBUS communication are documented.

  4. 4

    4. Test the drive with a known-good PROFIBUS communication board (CB) if available, to rule out a hardware fault on the existing board.

  5. 5

    5. Temporarily disconnect the PROFIBUS cable from the X100 terminal and restart the drive to see if the fault persists, which helps isolate bus issues from internal hardware.

Browse all codes in this manual (109)