A00701

PROFIBUS: DoubleWord error

Siemens · SINAMICS G120

What does A00701 mean?

This alarm signals an error within the PROFIBUS double word reference table, which is critical for data exchange. This typically indicates a corruption or inconsistency in how PROFIBUS data is mapped within the drive, potentially leading to incorrect data interpretation.

Common Causes

  • Mismatch in the PROFIBUS data length or data type configuration between the master (PLC) and the drive (slave) for double-word (32-bit) parameters.
  • Incorrect indexing or mapping of PROFIBUS process data (PZD) in the drive parameters (e.g., P2051, P2053) relative to the PLC's configuration.
  • Data corruption on the PROFIBUS bus due to excessive noise, improper shielding, or termination issues, affecting multi-byte data integrity.
  • Firmware incompatibility between the drive and the PROFIBUS master concerning how specific double-word values are processed.
  • Faulty internal PROFIBUS interface hardware within the drive, leading to errors in assembling/disassembling double-word telegrams.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify the PROFIBUS process data (PZD) mapping for both send (P2051) and receive (P2053) directions in the drive, ensuring double-word parameters align with the PLC.

  2. 2

    2. Compare the data types and lengths configured for PROFIBUS communication in the PLC program with the drive's specifications for each PZD.

  3. 3

    3. Inspect the PROFIBUS cable, connectors, and termination resistors (e.g., X101) for proper installation and absence of damage to minimize data corruption.

  4. 4

    4. Temporarily simplify the PROFIBUS telegrams to single-word (16-bit) communication (if possible) to isolate the double-word issue.

  5. 5

    5. Check for and install any available firmware updates for the drive that address PROFIBUS communication stability or data handling.

  6. 6

    6. Utilize a PROFIBUS analyzer to capture and inspect the raw telegram data to identify where the double-word errors are occurring.

Browse all codes in this manual (109)
Verified technical data. Last updated: March 2026

Related Faults

Siemens Error A00701: PROFIBUS: DoubleWord error — Troubleshooting Guide | ErrorLib