F00055
BOP-EEPROM Fault
Siemens · SINAMICS G120 Variable Speed Drive
What does F00055 mean?
A read or write failure occurred in the EEPROM of the Basic Operator Panel (BOP) during parameter cloning or saving. This could be due to a faulty BOP, an EEPROM that is too small for the stored parameters, or an incompatibility, leading to an inability to store or retrieve non-volatile parameters essential for drive configuration.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If r0949 = 9160, ensure the parameter set being loaded is compatible with the drive's EEPROM capacity, possibly by using a BOP that stores smaller parameter configurations.
- 4
Consider replacing the Basic Operator Panel (BOP) if the fault persists and is not related to EEPROM size.
Source: Siemens SINAMICS G120 Variable Speed Drive