F01663
Copying the SI parameters rejected
Siemens · SINAMICS G120 Safety Functions
What does F01663 mean?
The attempt to copy Safety Integrated (SI) parameters was rejected. This can happen if p9700 is not 0, or if safety functions (p9501, p9601) are active, preventing critical parameter changes. This can lead to an inconsistent or un-saved configuration, especially after modifying safety settings.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Start the copy function again by entering the corresponding value into p9700.
Source: Siemens SINAMICS G120 Safety Functions
View Official PDF