F30022
Power unit: Monitoring U_ce
Siemens · DCM
What does F30022 mean?
The monitoring of the collector-emitter voltage (U_ce) in the power unit's semiconductors has detected an abnormal condition. This often indicates a short circuit at the power unit output, a defective IGBT, a problem with the IGBT gating module's power supply (24V), or an interrupted fiber-optic cable. This is a critical fault that can lead to immediate and severe damage to the power unit's IGBTs if not addressed.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check the power cable connections at the drive output for any short-circuits between phases or to ground.
- 4
If suspected, identify and replace any defective semiconductor (IGBT) within the power unit.
Source: Siemens DCM
View Official PDF