F07806
Drive: Regenerative power limit exceeded (F3E)
Siemens · DCM
What does F07806 mean?
For PM250 and PM260 blocksize power units, the regenerative rated power (r0206[2]) was continuously exceeded for more than 10 seconds. This indicates that the drive is generating excessive energy back into the DC bus or supply, which can lead to overvoltage and potential damage if the regeneration capability is insufficient.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Consider upgrading to a power unit with a higher regenerative feedback capability if the application inherently produces significant regenerative energy.
- 4
For vector control applications, reduce the regenerative power limit in parameter p1531 to prevent the fault from triggering prematurely.
Source: Siemens DCM