F07016
Drive: Motor temperature sensor fault
Siemens · DCM
What does F07016 mean?
An error was detected during the evaluation of the motor temperature sensor (configured in p0601). Possible causes include a wire breakage (KTY: R > 2120 Ohm), the sensor not being connected, or a measured resistance that is too low due to a short circuit (PTC: R < 20 Ohm, KTY: R < 50 Ohm). If alarm A07015 was present, this fault was output after the timer p0607 expired, indicating a prolonged issue.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
For induction motors, if temperature monitoring is not critical or desired for the application, deactivate the temperature sensor fault by setting parameter p0607 = 0.
Source: Siemens DCM