F07016

Drive: Motor Temperature Sensor Fault

Siemens · DAsl Diagnostics and Alarms

What does F07016 mean?

A critical error was detected during the evaluation of the motor temperature sensor (configured via p0600 and p0601). This fault signifies severe problems like wire breakage, a disconnected sensor (KTY resistance > 1630 Ohm), or measured resistance that is too low (PTC < 20 Ohm, KTY < 50 Ohm). This fault often occurs after alarm A07015 has been active for the time specified in p0607, posing a direct risk of motor overheating and damage if left unaddressed.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    For induction motors, consider de-activating the temperature sensor fault (p0607 = 0) only if alternative, reliable thermal monitoring is in place and safe to do so.

Source: Siemens DAsl Diagnostics and Alarms
View Official PDF