F01600

SI CU: Error During DRIVE-CLiQ Communication

Siemens · DAsl Diagnostics and Alarms

What does F01600 mean?

The drive-integrated 'Safety Integrated' (SI) function on the Control Unit (CU) has detected an error in the sign-of-life of safety data between the CU and a Motor Module (MM), or a time slice overflow of the safety software occurred. This indicates a critical communication error that initiates a STOP A, posing a safety risk and halting operation until resolved.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Check for and diagnose any DRIVE-CLiQ communication errors between the Control Unit and the implicated Motor Module, carrying out diagnostics routines.

  2. 4

    De-select any drive functions that are not absolutely necessary and reduce the number of active drives if possible to reduce system load.

  3. 5

    Review the electrical cabinet design and cable routing for adherence to EMC compliance standards to mitigate electromagnetic interference.